Start-up and shutdown of diesel generators

Starting and stopping of diesel generator sets are divided into two forms, one is manual test, and the other is automatic switching control.

I. Manual test machine

1. Manual start of the diesel generator set: After testing the alarm system is normal, cut the control switch to the manual (MAN) position and the diesel generator set can start by itself.
2. Stopping the diesel generator set: Turn the control switch to the STOP position or press the red emergency stop button to stop the generator operation. In an emergency, you can press the emergency stop button directly to force a shutdown. If the red emergency stop button is pressed, it must return to its original position, otherwise the generator will not start.

Second, automatic switching control

1. Switch the control switch to AUTO, and cooperate with the power automatic switch (ATS). The control switch must also be used in the automatic position. When the mains power is stopped, A · T · S will give the start signal to the generator control. System, the generator will start automatically.
2. When the control switch is switched to STOP, or remains in automatic, but ATS sends a stop signal when the mains power is restored, the diesel generator set will automatically stop. Note: When the diesel generator set in operation is automatically shut down due to a fault (overspeed, high water temperature, low oil pressure, etc.), you must press the fault reset button to prepare for restart after troubleshooting.

Source: Zhongsheng Generator Time: 2017/3/22